MENU
TEP-4300

TEP-4300 Extinguishing Panel

Designed especially for use in environments with irreplaceable and important items, the TEP-4300 Fire Extinguishing panel provides many advantages and convenience to users and installers with features such as programmable 5 zone capacity, user-friendly 128x64 LCD display, 4000 time-stamped event logs etc. Alternatively, the system can be connected to the cloud-based Mosaic platform (web, mobile) via LTE.

  • General Features
  • Technical Specifications
  • Downloads
  • Fully compliant with EN 12094-1, EN 54-2, EN 54-4 
  • 5 Fire Detection Zone 
  • 1 Extinguishing Output 
  • Multiple Solenoid and Actuator Support 
  • 6 Monitoring Input (Abort, Hold, Mode Select, Manual Release, Low Pressure, Flow Switch) 
  • 6 Relay Output (Fault, Fire, Local Fire, First Stage, Second Stage, Extract) 
  • 3 Sounder Output (2 for Fire, 1 for extinguishing) 
  • 4 Remote Input (Reset, Fault, Silence, Alarm) 
  • Detailed monitoring of Fire and Extinguishing processes via LCD 
  • MCP Alarm Detection Support 
  • Adjustable fire output delay times 
  • Adjustable extinguishing process times 
  • 90 different zone combinations 
  • Real Time Clock 
  • Multi-language Support 
  • TEM-4385 Terminator Support (Up to 2)
  •  TXM-4380 I/O Expander Module Support 
  • TXM-5474 LTE Module Support 
  • Time Stamped 4000 Log Memory 
  • 128*64 LCD Display 
  • 35 Led Indicator 
  • 3 user access level 
  • Export Logs, Import Configurations, Software Update (via USB) 
  • Teknim Mobile Application Support 
  • Teknim Mosaic Web Support 
Internal Power Supply 24 Vdc nominal
Battery Type 2x 12 V 7 Ah
Battery Internal Resistance Fault 1.5 Ω (Ri max.)
Charger Temperature Compensation YES
Earth Fault Monitoring YES
Mains supply/battery charger monitoring YES
I min. 130 mA
I max. a 600 mA
I max. b 3 A
Number of Zone 5
Max number of detectors per zone 32
End-of-line resistor 4k7 Ω, %5, ¼ W
Output rating 18-27.6 Vdc
Number of sounder outputs 3
End-of-line resistor 4k7 Ω, %5, ¼ W
Number of monitoring inputs 6
End-of-line resistor 4k7 Ω, %5, ¼ W
Number of remote inputs 4
Activation condition Short circuit
Number of relays 6
Relay contact 30 Vdc, 2 A max.
Extinguishing release 17.5-27.6 Vdc @ 1 A
Short circuit and open circuit monitoring YES
End-of-line output TEM-4385 Terminator
Release time delay 0-60 seconds
Release duration 1-300 seconds
Flooding time 60-1740 seconds
Battery fuse 30 Vdc, 5 A
Aux output fuse 30 Vdc, 500 mA
Sounder circuit fuse 30 Vdc, 300 mA
Mains supply fuse 30 Vdc, 5 A
Extinguishing output fuse 30 Vdc, 5 A
TXM-4380 I/O Expander Module TXM-5474 LTE Module RS-485
IP Rating IP30
Temperature range -5 °C ~ +40 °C
Relative humidity 95% RH max.